0449 Gusseting Device Thermal Overload

Gusseting Device Thermal Overload

 

The converter thermal model indicates that the temperature has exceeded the factory set thermal capacity value of 110%.

  • Reduce the start-up times of all drives that share the DC bus.
  • Reduce number of shared DC follower drives.
  • Reduce duty-cycle of the command axis control. Thermal overload of the inverter. User limit value exceeded.

The converter thermal model indicates that the temperature has exceeded the user-defined limit value for the thermal overload.

  • Reduce the start-up times of all drives that share the DC bus.
  • Reduce number of shared DC follower drives.
  • Reduce duty-cycle of the command axis control.
  • Increase the inverter thermal overload attribute value.

The thermal model for the power transistors indicates that the temperature has exceeded the user-defined limit value for the thermal overload of the inverter.

  • Reduce the speed or extend the time in the command profile.
  • Increase the inverter thermal overload attribute value. Thermal overload of the inverter. Factory-set limit value exceeded.

Thermal overload of the bus regulator. Factory-set limit value exceeded. The thermal brake model has exceeded its factory set thermal capacity limit.

  • Modify the duty cycle of the application.
  • Add an external brake for additional capacity.
  • Add a capacitor module if needed.

Thermal overload of the bus regulator. User limit value exceeded. The thermal brake model has exceeded the thermal capacity limit of the user- defined limit value for the thermal overload of the bus regulator.

  • Modify the duty cycle of the application.
  • Add an external brake for additional capacity.
  • Increase the attribute value of the user-defined limit value for the thermal overload.
  • Add a capacitor module if needed.

Thermal overload of the inverter. Factory-set limit value exceeded. The thermal model for the power transistors indicates that the temperature has exceeded the factory set thermal capacity value of 110%.

  • Reduce the speed or extend the time in the command profile. Thermal overload of the inverter. User limit value exceeded.

------------------------------------------------------------------------